I-DUCO L2003592-F Modbus TCP

Imininingwane Yomkhiqizo

  • Igama Lomkhiqizo: Ibhodi Lokuxhumana le-Duco
  • Amamodeli Asekelwe: DucoBox Silent Connect, DucoBox Focus, DucoBox Energy
  • Modbus Subset Support: HEX 0x03, 0x04, 0x06, 0x10
  • Modbus Component Interface: TCP on port 502

Imiyalo yokusetshenziswa komkhiqizo

Ukusebenza namarejista/amapharamitha
The DucoBox Silent Connect, Focus, and Energy support the following Modbus subset functions:

  • Funda amarejista amaningi okubambile (HEX 0x03)
  • Funda amarejista amaningi we-INPUT (HEX 0x04)
  • Write a single HOLDING register (HEX 0x06)
  • Bhala amarejista amaningi okubambile (HEX 0x10)
    Input registers are read-only 16-bit variables, while holding registers are read/write 16-bit variables. The Modbus address can be set via the Display menu, Duco Installation App, or Duco Network Tool.

Ukuxhumana ne-Control Unit
The external control unit communicates with each component through read parameters (INPUT) and write parameters (HOLDING).

  • Funda Amapharamitha (INPUT): Ventilation system type, ventilation status, indoor air quality based on relative humidity, indoor air quality based on CO2 value, etc.
  • Bhala Amapharamitha (HOLDING): Ventilation status, component identification, etc.
    It is recommended to read the current value before performing a write action to adjust the value. There are limits on write actions to prevent excessive writing.

Kuphelileview ye-Parameters
Ngezansi i-overview of the INPUT and HOLDING parameters for the ventilation system and its components:

Bhalisa INPUT (Funda ipharamitha) Ukuguqulwa Kwedatha Isicelo Imvamisa Yenhlolovo Enconyiwe
0020 Izinga lokushisa ODA Ibonisa izinga lokushisa lomoya wokuhlinzeka kusuka ngaphandle kuya ku
iyunithi (Umoya Wangaphandle).
I-DucoBox Amandla 1/min

Isingeniso

  • The Modbus interface on DUCO systems (via the Duco Connectivity Board option on a DucoBox)1 allows an external controller or building management system to communicate with the DUCO ventilation system.
  • That way, you can retrieve info about the ventilation network via read parameters or input registers, or read or adjust settings via write parameters or holding registers.
  • The supported protocol is Modbus TCP over Ethernet or Wi-Fi via the Duco Connectivity Board. The information in this document is valid from API version v2.5 onwards.

Working registers/parameters

  • The DucoBox Silent Connect, Focus, and Energy support the following Modbus subset:
    I-HEX DEC SUPPORT FUNCTION
    0x03 3 Funda amarejista amaningi okubaMBA
    0x04 4 Funda amarejista amaningi we-INPUT
    0x06 6 Write a single HOLDING register
    0x10 16 Write multiple HOLDING registers
  • Here, input registers are 16-bit read-only variables, and holding registers are 16-bit read/write variables. Combined consecutive registers are not used. The Duco Connectivity Board functions as a Modbus component via TCP on port 502. The Modbus address can be set via the Display menu (see information sheet L8000002), the Duco Installation App, or the Duco Network Tool.
  • The external control unit communicates with each component (node) through read parameters (INPUT) and write parameters (HOLDING).
    • Read parameters (INPUT): ventilation system type, ventilation status, indoor air quality based on relative humidity, indoor air quality based on CO2 value, …
    • Write parameters (HOLDING): ventilation status, identification (of components), …
      Qaphela: Read parameters can be read without restriction. There are, however, two important limits to writing actions:
      1. A daily limit of 200 write actions. From a second supply or extraction zone, 100 write actions are added per additional zone.
      2. A periodic limit of one write action every 2 seconds.
  • It is recommended to use a logic that first reads the current value before determining whether a new write action is needed to adjust the value.
  • Indawo ngayinye nemingcele yayo yabelwe ikhodi: XXyy (XX=inombolo yenodi, yy=inombolo yepharamitha).DUCO-L2003592-F-Modbus-TCP-fig-1
  • This allows all values to be read and controlled from the external control unit. There are specific parameters for each component.
    Qaphela
    • Due to a difference in some Modbus implementations compared to the official specification (on which our implementation is based), an address shift of ‘1’ may occur for the read and write parameters.
      E.g.: read address ‘20’ will become ‘19’.
    • For any box type (Silent Connect, Focus, Energy), this can be resolved via the Duco Installation App or the Duco Network Tool under tab > Tree view-Settings-external settings. With the DucoBox Focus, moreover, this can be solved by setting ‘ > ‘RegOffs’ to ‘1’ under > CONFIG > Modbus in the Display menu. With the DucoBox Energy also possible via ‘Register Offset’ under > Setting > Modbus in the advanced menu.

Kuphelileview kwamapharamitha

The overview is grouped into three sections:

  • Parameters that are only supported at the system level.
  • Parameters that are only supported by the DucoBox.
  • Parameters that are supported by the nodes (components).
    Ngezansi i-overview we-INPUT kanye nemingcele yokubamba kokubili isistimu yokukhipha umoya kanye nezingxenye.

Amapharamitha wesistimu:

INPUT

(funda ipharamitha)

Bhalisa Idatha Ukuguqulwa Isicelo Imvamisa yohlolo olunconyiwe
0020 Izinga lokushisa ODA Displays the temperature of the supply air from outside to the unit (Outdawu Air). °C / 10 I-DucoBox Amandla 1 / iminithi
0021 SUP temperature displays the temperature of the supply air from the unit to the home (Supply Air). °C / 10 I-DucoBox Amandla 1 / iminithi
0022 Izinga lokushisa I-ETA Displays the temperature of the exhaust air from the home to the unit (Extract Air). °C / 10 I-DucoBox Amandla 1 / iminithi
0023 Izinga lokushisa EHA Displays the temperature of the exhaust air from the unit to the outside (Exhaust Air). °C / 10 I-DucoBox Amandla 1 / iminithi
0024 Izinga lokushisa langaphandle measured via the weather station. °C / 10 I-DucoBox enesiteshi sezulu 1 / iminithi
0025 Isivinini somoya
Measured via the weather station.
Idesimetha/yesibili I-DucoBox enesiteshi sezulu 1 / iminithi
0026 Imvula
Measured via the weather station.
0 = Cha (Amanga) 1 = Yebo (Iqiniso) I-DucoBox enesiteshi sezulu 1 / iminithi
0027 Light intensity south was measured via the weather station. I-Kilolux I-DucoBox enesiteshi sezulu 1 / iminithi
0028 Light intensity east was measured via the weather station. I-Kilolux I-DucoBox enesiteshi sezulu 1 / iminithi
0029 Light intensity west was measured via the weather station. I-Kilolux I-DucoBox enesiteshi sezulu 1 / iminithi
0030 Local API Version Displays the local API version. Inombolo ephelele Example: 2.4 becomes 204.

Public API version ‘X.Y’ becomes Modbus = X · 100 + Y

DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / ngosuku
0031 Remaining write actions: Displays the number of corrective commands until midnight. Inombolo ephelele DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / iminithi
  • Negative temperatures are displayed as a number greater than 32767.
  • To display this value correctly, you need to implement some logic to convert the value.
  • The formula is: (value-65536)/ 10
  • Example:
    • If(ModBusInputRegisterValue >= 32768)
    • Temp = (ModbusInputRegisterValue – 65536)/10
      Okunye
    • Temp = ModbusInputRegisterValue/10
      Qeda

Amapharamitha we-DucoBox:

INPUT

(funda ipharamitha)

Bhalisa Idatha Ukuguqulwa Isicelo Imvamisa yohlolo olunconyiwe
0100 Uhlobo lwesistimu
Indicates the type of ventilation system
17 = DucoBox DucoBox Silent Connect DucoBox Focus DucoBox Energy isikhathi esisodwa
0102 Isikhathi esisele Imodi yamanje Yokungenisa umoya
Ibonisa isikhathi esisele lapho i-DucoBox izokhipha umoya ngayo kule modi
Imizuzwana DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / iminithi
0103 Izinga lokugeleza liqhathaniswa neleveli eqondiwe
Ibonisa imodi yokungenisa umoya yangempela yezoni lapho ingxenye etholakala khona
Iphesentitage DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / iminithi
0104 Ikhwalithi yomoya wasendlini esekelwe ku-RH
Average indoor air quality based on measured relative humidity
100 %

95 %

Ikhwalithi yomoya yasendlini enhle kakhulu Box sensor DucoBox Silent Connect

Box sensor DucoBox Energy

1 / iminithi
90 %

80 %

65 %

Ikhwalithi yomoya yasendlini enhle
50 %

35 %

Ikhwalithi yomoya yasendlini eyamukelekayo okwesikhashana
20 %

5 %

Ikhwalithi yomoya yasendlini ephansi
0105 Indoor air quality based on CO2
Average indoor air quality based on measured CO2 value
100 % Very good indoor air 95 %   quality

90 %

Box sensor DucoBox Silent Connect

Box sensor DucoBox Energy

1 / iminithi
85 %

80 %   Good indoor air quality 75 %

70 %

65 %   Temporarily acceptable 60 %   indoor air quality

55 %

50 %

45 %

40 %   Poor indoor air quality 35 %

35 %

0106 Ventilation status
Indicates the status of ventilation
 

0 = KULUNGILE

1 = Iphutha

2 = Ayisebenzi

DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / iminithi
0107  Filter Time Remaining
Indicates remaining filter life
Izinsuku I-DucoBox Amandla 1 / ngosuku
0108  

Hlunga isimo
Indicates the status of the filter

0 = KULUNGILE

1 = Filter is dirty 2 = Inactive

I-DucoBox Amandla 1 / iminithi
0109 Umswakama
Indicates the measured humidity value.
I-RH (%) (umswakama ohlobene) DucoBox Silent Connect DucoBox Focus DucoBox Energy

+ minimum

1 humidity sensor

1 / iminithi
10 % Ikhwalithi yomoya yasendlini ephansi
15 %
20 %   Temporarily acceptable
25 %   indoor air quality
30 % Ikhwalithi yomoya yasendlini enhle
35 %
40 %
Ikhwalithi yomoya yasendlini enhle kakhulu
45 %

50 %

55 %

60 % Ikhwalithi yomoya yasendlini enhle
65 %
70 %
75 %   Temporarily acceptable
80 %   indoor air quality
85 % Ikhwalithi yomoya yasendlini ephansi
0110 CO2
Indicates the measured CO2  value.
I-CO2 (ppm) DucoBox Silent Connect DucoBox Focus DucoBox Energy

+ ubuncane benzwa ye-CO2 engu-1

1 / iminithi
<800

800

900

Ikhwalithi yomoya yasendlini enhle kakhulu
1000

1100

1200

Ikhwalithi yomoya yasendlini enhle
1250

1300

1350

1400

1450

Ikhwalithi yomoya yasendlini eyamukelekayo okwesikhashana
1500

1550

1600

> 1600

Ikhwalithi yomoya yasendlini ephansi
UKUBAMBA

(read/write parameter)

Bhalisa Idatha Ukuguqulwa Isicelo Imvamisa yohlolo olunconyiwe
0100 Imodi yokungenisa umoya

Here, the ventilation mode can be adjusted.

Conversions 11 through 16 are used to maintain manual modes longer.

Okwesiboneloample, Manual 1 (conversion 4) is set to duration t by default. For Manual 1 x 2 (conversion 11), the mode t x 2 (= 2 x standard duration) will be maintained and for Manual

1 x 3 (conversion 14), the mode t x 3 (= 3 x standard duration) will be maintained.

0 = NGOKUZENZAKALELAYO

4 = Manual 1

5 = Manual 2

6 = Manual 3 7 = Not at home

8 = Permanent 1

9 = Permanent 2

10 = Permanent 3

11 = Manual 1 x 2

12 = Manual 2 x 2

13 = Manual 3 x 2

14 = Manual 1 x 3

15 = Manual 2 x 3

16 = Manual 3 x 3

DucoBox Silent Connect DucoBox Focus DucoBox Energy 1 / iminithi
xx01 Ukuhlonza: Here, a component can be identified. This will light up blue. 0 = Ukubonakala Kwenodi KUVALIWE 1= Ukubona Ngeso leNodi KUVULIWE DucoBox Silent Connect DucoBox Focus DucoBox Energy One-time, read before write. (Read and check before writing)
0102 Izinga lokushisa lokunikezela target zone 1
Lapha, izinga lokushisa lokunethezeka le-SUP zone 1 lingalungiswa
°C / 10 I-DucoBox Amandla One-time, read before write. (Read and check before writing)
0103 Izinga lokushisa lokunikezela target zone 2
Lapha, izinga lokushisa lokunethezeka le-SUP zone 2 lingalungiswa
°C / 10 I-DucoBox Amandla One-time, read before write. (Read and check before writing)
0104 Izinga lokushisa lokunikezela target zone 3
Lapha, izinga lokushisa lokunethezeka le-SUP zone 3 lingalungiswa
°C / 10 I-DucoBox Amandla One-time, read before write. (Read and check before writing)
0105 Izinga lokushisa lokunikezela target zone 4
Lapha, izinga lokushisa lokunethezeka le-SUP zone 4 lingalungiswa
°C / 10 I-DucoBox Amandla One-time, read before write. (Read and check before writing)

Amapharamitha weNode:

INPUT

(funda ipharamitha)

Bhalisa Idatha Ukuguqulwa Isicelo Imvamisa yohlolo olunconyiwe
xx00 Uhlobo lwesistimu
Indicates the type of ventilation system
0 = Akwaziwa

7 = DucoTronic window ventilator 8 = User controller RF/BAT

9 = User controller RF/Wired 10 = Humidity Room sensor 12 =CO2 Room sensor

13 = Sensorless Control Valve

14 = Humidity Control Valve 16 = CO2 Control Valve

18 = Switch Sensor

22 = iAV Control valve 23 = iAV Humidity

25 = iAV CO2

27 = Iyunithi yokulawula

28 =CO2/RH control valve

29 = User Controller ‘Sun Control’

30 = User Controller ‘Ventilative Cooling’

31 = External multi-zone valve 35 = Humidity box sensor

37 = CO2 Box Sensor 38 = Motor relay

39 = Duco Weather Station or Outdoor Temperature Sensor 40 = Modbus motor

41 = Digital input 42 = Digital output 44 = Modbus relay 45 = Perilex

46 = Relay output

User controller Room sensor Box sensor Control valve Switch sensor

I-electronic window ventilator

isikhathi esisodwa
xx02 Isikhathi esisele Imodi yamanje Yokungenisa umoya
Ibonisa isikhathi esisele lapho i-DucoBox izokhipha umoya ngayo kule modi
Imizuzwana Isilawuli somsebenzisi Inzwa yegumbi Control valve Shintsha inzwa 1 / iminithi
xx03 Izinga lokugeleza liqhathaniswa neleveli eqondiwe
Ibonisa imodi yokungenisa umoya yangempela yezoni lapho ingxenye etholakala khona
Iphesentitage Control valve, Electronic window ventilator 1 / iminithi
xx04 Ikhwalithi yomoya wasendlini esekelwe ku-RH
Average indoor air quality based on measured relative humidity
100 %

95 %

Ikhwalithi yomoya yasendlini enhle kakhulu I-valve yokulawula inzwa yegumbi 1 / iminithi
90 %

80 %

65 %

Ikhwalithi yomoya yasendlini enhle
50 %

35 %

Ikhwalithi yomoya yasendlini eyamukelekayo okwesikhashana
20 % Ikhwalithi yomoya yasendlini ephansi
xx05 Indoor air quality based on CO2
Average indoor air quality based on measured CO2 value
100 % Very good indoor air 95 %   quality

90 %

I-valve yokulawula inzwa yegumbi 1 / iminithi
85 %

80 %   Good indoor air quality 75 %

70 %

65 %   Temporarily acceptable 60 %   indoor air quality

55 %

50 %

45 %

40 %   Poor indoor air quality 35 %

30 %

xx09 Umswakama
Indicates the measured humidity value.
I-RH (%) (umswakama ohlobene) Humidity Room Sensor Humidity Box Sensor

Ivalvu Yokulawula Umswakama

I-electronic window ventilator

1 / iminithi
10 %

15 %

Ikhwalithi yomoya yasendlini ephansi
20 %

25 %

Ikhwalithi yomoya yasendlini eyamukelekayo okwesikhashana
30 %

35 %

40 %

Ikhwalithi yomoya yasendlini enhle
45 %

50 %

55 %

Ikhwalithi yomoya yasendlini enhle kakhulu
60 %

65 %

70 %

Ikhwalithi yomoya yasendlini enhle
75 %

80 %

Ikhwalithi yomoya yasendlini eyamukelekayo okwesikhashana
 

85 %

Ikhwalithi yomoya yasendlini ephansi
xx10 CO2
Indicates the measured CO2  value.
I-CO2 (ppm) I-CO2 Room Sensor CO2 Box Sensor CO2 Control Valve 1 / iminithi
< 800 Very good indoor air quality 800

900

1000
1100   Good indoor air quality
1200
1250
1300   Temporarily acceptable

1350   indoor air quality

1400
1450
1500

1550

1600

> 1600

 

Ikhwalithi yomoya yasendlini ephansi

UKUBAMBA

(read/write parameter)

Bhalisa Idatha Ukuguqulwa Isicelo Imvamisa yohlolo olunconyiwe
xx00 Imodi yokungenisa umoya

Here, the ventilation mode can be adjusted.

Conversions 11 through 16 are used to maintain manual modes longer.

Okwesiboneloample, Manual 1 (conversion 4) is set to duration t by default. For Manual 1 x 2 (conversion 11), the mode t x 2 (= 2 x standard duration) will be maintained and for Manual

1 x 3 (conversion 14), the mode t x 3 (= 3 x standard duration) will be maintained.

0 = NGOKUZENZAKALELAYO

4 = Manual 1

5 = Manual 2

6 = Manual 3 7 = Not at home

8 = Permanent 1

9 = Permanent 2

10 = Permanent 3

11 = Manual 1 x 2

12 = Manual 2 x 2

13 = Manual 3 x 2

14 = Manual 1 x 3

15 = Manual 2 x 3

16 = Manual 3 x 3

User controller Room sensor Box sensor Control valve

I-electronic window ventilator

1 / iminithi
xx01 Ukuhlonza
Here, a component can be identified. This will light up blue.
0 = Ukubonakala Kwenodi KUVALIWE 1= Ukubona Ngeso leNodi KUVULIWE User controller, Room sensor, Control valve,e Switch sens, or Electronic window ventilator One-time, read before write. (Read and check before writing it)

Imininingwane ejwayelekile

Ukuze uthole ukuthi yimaphi ama-node akhona kunethiwekhi, ungakwazi (ngokuzithandela) ukusebenzisa amarejista we-INPUT angezansi. Ngaphandle kwalokho, ungaskena wonke amarejista.
Example:

DUCO-L2003592-F-Modbus-TCP-fig-2

 

BHALISA

 

IDATHA

OKUNCONYWA KWE-SURVEY FREQUENCY
0000 Bit field indicating which node numbers between 1 and 15 are occupied in the network  

 

 

 

isikhathi esisodwa

0001 Bit field indicating which node numbers between 16 and 31 are occupied in the network
0002 Bit field indicating which node numbers between 16 and 31 are occupied in the network
0003 Bit field indicating which node numbers between 48 and 63 are occupied in the network
0004 Bit field indicating which node numbers between 64 and 79 are occupied in the network
0005 Bit field indicating which node numbers between 80 and 95 are occupied in the network
0006 Bit field indicating which node numbers between 96 and 111 are occupied in the network
0007 Bit field indicating which node numbers between 112 and 127 are occupied in the network
0008 Bit field indicating which node numbers between 128 and 143 are occupied in the network

imibuzo ejwayelekile ukubuzwa

How can I set the Modbus address for the Duco Connectivity Board?

The Modbus address can be set via the Display menu, Duco Installation App, or Duco Network Tool.

What are the limits on write actions for the Duco Connectivity Board?

There is a daily limit of 200 write actions, with additional actions allowed based on the number of supply or extraction zones. Additionally, there is a periodic limit of one write action every 2 seconds.