  • Igama Lomkhiqizo: I-Remote User Interface
  • Compatibility: MicroTech Applied Rooftops, Air and Water-CooledChiller unit controllers
  • Supported Models: Rebel Packaged Rooftop, Self-Contained Systems, and various other models

Isingeniso

Ulwazi oluvamile

  • Le manuwali ichaza indlela yokufaka nokusebenzisa isixhumi esibonakalayo somsebenzisi esikude ukuze sisetshenziswe ne-MicroTech Applied Rooftops kanye nezilawuli zeyunithi ye-Air and Water-Cooled chiller kusuka ku-Daikin Applied.
  • Ukuze uthole ukwesekwa kobuchwepheshe ophahleni lwendlu noma izilawuli zeyunithi ezizimele, xhumana ne-Daikin Applied Air Technical Response Center ku- 800-432-1342 (AAHTechSupport@daikinapplied.com).
  • Ukuze uthole ukwesekwa kwesilawuli seyunithi yokupholisa, xhumana ne-Daikin Applied Chiller Technical Response Center kokuthi 800-432-1342 (CHLTechSupport@daikinapplied.com).
  • For technical support on PreciseLine unit controllers, contact the Daikin Applied Air Technical Response Center at 800-432-3928 (ATSTechSupport@daikinapplied.com)

Ulwazi Lomkhiqizo
Isixhumi esibonakalayo somsebenzisi esikude siklanyelwe ukuboniswa, ukumiswa kwesistimu, ukusetha, nokuphathwa kwezilawuli zeyunithi ye-MicroTech:

Amamodeli we-MicroTech Unit Controller
I-Rebel® Packaged Rooftop Wonke amamodeli
I-Rebel Packaged Rooftop Wonke amamodeli
Izinhlelo Ezizimele Amamodeli we-SWT ne-SWP
Maverick® II Commercial Rooftop Model MPS
I-Pathfinder® Air-Cooled Screw Chiller Amamodeli AWS kanye AWV
I-Trailblazer® Air-Cooled Scroll Compressor Chiller Amamodeli we-AGZ-D ne-AGZ-E
Magnitude® Water-Cooled Chiller Model WME, B Vintage
I-Navigator® Water-Cooled Screw Chiller Imodeli ye-WWV/TWV
I-Trailblazer® Air-Cooled Chiller Imodeli ye-AMZ
I-PreciseLine® Air Handler Wonke amamodeli

Ngokungeziwe kukhiphedi/isibonisi sesilawuli esifakwe iyunithi, amasistimu okulawula amayunithi e-MicroTech angahlonyiswa ngesixhumi esibonakalayo somsebenzisi esikude esisingatha kufika kumayunithi ayisishiyagalombili esibonakalayo ngasinye. Isixhumi esibonakalayo somsebenzisi esikude sinikeza ukufinyelela ekuxilongweni kweyunithi nokulungiswa kokulawula okufana nesilawuli esifakwe iyunithi.

Izici

  • Push-and-roll navigation wheel with an 8-line by 30- character display format
  • Operating conditions, system alarms, control parameters and schedules are monitored
  • RS-485 or KNX interface for local or remote installation
  • Power from controller, no additional power supply necessary
  • Supports panel mounting and wall mounting

Imilayezo Yolwazi Oluyingozi

INGOZI
Ingozi ikhombisa isimo esiyingozi, esizoholela ekufeni noma ukulimala okubi uma singagwenywa.

ISEXWAYISO
Isexwayiso sibonisa izimo ezingaba yingozi, ezingaholela ekulimaleni kwempahla, ukulimala komuntu siqu, noma ukufa uma kungagwenywa.

ISEXWAYISO
Isexwayiso sibonisa izimo ezingaba yingozi, ezingase zibangele ukulimala okuncane noma ukulimala kwemishini uma kungagwenywa.

ISAZISO
Isaziso sibonisa izinqubo ezingahlobene nokulimala ngokomzimba.

Imibhalo Eyisethenjwa

Inombolo Inkampani Isihloko Umthombo
 I-IOM 1202  I-Daikin isetshenzisiwe I-Pathfinder Chiller Model AWS Ukufakwa, Ukusebenza, kanye Nemanuwali Yokulungisa            www.DaikinApplied.com
 I-IOM 1206  I-Daikin isetshenzisiwe Ukufakwa kwe-Trailblazer Chiller Model AGZ, Imanuwali Yokusebenza Nesondlo
 I-IOM 1242  I-Daikin isetshenzisiwe I-Pathfinder Model AWV Chiller Installation, Operation, and Maintenance Manual
 I-IOMM 1033  I-Daikin isetshenzisiwe Imodeli ye-Magnitude WME, B vintage I-Magnetic Bearing Centrifugal Chiller Installation, Operation, and Maintenance Manual
 I-IOM 1264  I-Daikin isetshenzisiwe Imodeli Ye-Navigator WWV/TWV Ukufakwa Kwe-Chiller Epholile Ngamanzi, Ukusebenza, kanye Nemanuwali Yokulungisa
I-IOM 1243 I-Daikin isetshenzisiwe Trailblazer Chiller Model AMZ
 OM1382  I-Daikin isetshenzisiwe I-Rebel Commercial Packaged Rooftop Systems, Ibhukwana Lokusebenza kanye Nesondlo
 OM1373  I-Daikin isetshenzisiwe I-Rebel Applied Rooftop Systems, Imanuwali Yokusebenza kanye Nesondlo
 OM1357  I-Daikin isetshenzisiwe PreciseLine Air Handler, Operation and Maintenance Manual

Idatha Yengxenye

Okujwayelekile
Umfanekiso 1 ubonisa imininingwane yedizayini yehadiwe yesixhumi esibonakalayo somsebenzisi esikude.
Isakhiwo somzimba sisonke sihlanganisa:

  • 5.7 × 3.8 × 1 in (144 × 96 × 26 mm) size
  • 9.1 oz (256.7 g) weight, excluding packaging
  • Izindlu zepulasitiki

Amandla

  • Supplied by the MicroTech unit controller for direct connection
  • Separate 24V DAC power supply, optional for daisy chain connections, Max 85 mA

QAPHELA: Xhumana noma i-Daikin Applied Air Technical Response Centre ku 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com) if a separate power supply is desired.

Bonisa

  • LCD type FSTN
  • Resolution dot-matrix 96 x 208
  • Backlight blue or white, user selectable

Izimo Zemvelo

  • Operation EC 721-3-3
  • Temperature -40…158°F (-40…+70°C)
  • Restriction LCD -4…140°F (-20…+60°C)
  • Restriction Process-Bus -13…158°F (-25….+70°C)
  • Humidity < 90% RH (no condensation)
  • Air pressure Min. 10.2 psi (700 hPa), corresponding to max. 9843 ft (3000 m) above sea level

DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (1)

Ukufakwa

Ukufaka ngaphambilini
Sicela uqaphele okulandelayo ngaphambi kokukhweza nokufaka isixhumi esibonakalayo somsebenzisi wesilawuli kude.

Ukucatshangelwa kwendawo
Ukubekwa kwesixhumi esibonakalayo somsebenzisi esikude kuyadingeka ukuze kuqinisekiswe ukusebenza okufanele. Lapho ukhetha indawo, gwema okulandelayo:

  • Locations that are outside the operating temperature and humidity range (see Environmental Conditions.)
  • Mounting on rooftop without a careful site evaluation and confirmation
  • Walls that are subject to high vibration
  • Areas with high humidity exterior walls and other walls that have a temperature differential between the two sides
  • Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys, or other heat-generating equipment

Ukukhweza Surfaces
Ukuze ufakwe ngaphezulu, khweza isixhumi esibonakalayo somsebenzisi endaweni eyisicaba njengetshe leshidi noma ukhonkolo, iphaneli yokulawula, noma ibhokisi lokuhlangana likagesi.

  • If mounting onto sheet rock or plaster, use anchors, if necessary
  • For mounting in the unit controller panel, electrical junction box, or other metal enclosure, use the supplied magnets.

Izingxenye

Incazelo Inombolo Yengxenye
I-MicroTech Remote User Interface 1934080031,2
Connectors (using CE+ CE- connection option) 193410302
  1. Note that part number 193408001 is no longer available.
  2. For daisy-chaining unit controllers together, a 2-pin connector (PN 193410302), is required for each unit controller. The 2-pin connector is not required for direct-connecting unit controllers.

Ukuze uthole ihhovisi lendawo yangakini, vakashela www.DaikinApplied.com noma shayela u-800-37PARTS (800-377-2787).

DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (2) DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (3)

Ukukhweza nokuxhuma
Isigaba esilandelayo sichaza indlela yokukhweza isixhumi esibonakalayo somsebenzisi esikude futhi usixhume kusilawuli seyunithi esisodwa noma eziningi ze-MicroTech.

ISEXWAYISO
Ingozi yokukhishwa kwe-Electrostatic. Kungabangela ukulimala kwemishini.
Lesi sixhobo siqukethe izingxenye ze-elekthronikhi ezibucayi ezingalinyazwa ukukhishwa kwe-electrostatic ezandleni zakho. Ngaphambi kokuba uphathe imojuli yokuxhumana, udinga ukuthinta into ephansi, njengendawo ebiyelwe yinsimbi, ukuze ukhiphe amandla e-electrostatic emzimbeni wakho.

ISEXWAYISO
Ingozi yokushaqeka kukagesi. Kungabangela ukulimala komuntu siqu noma ukulimala kwemishini.
Lo mshini kufanele ubekwe phansi ngendlela efanele. Izisebenzi kuphela ezinolwazi ekusebenzeni kwempahla elawulwayo okufanele zenze ukuxhumana nesevisi kusilawuli seyunithi.

  1. Remove plastic cover (Figure 2).
  2. Mount the remote user interface. The remote user interface can be either panel mounted or wall mounted as shown in Figure 3. See Figure 4 and Figure 5 for terminal connections for each of the mounting locations.

Ifaka izintambo ku-Remote User Interface

Ukuxhuma i-interface yomsebenzisi ekude kusilawuli seyunithi ye-MicroTech kungenziwa ngezindlela ezimbili ezihlukene:

  1. Daisy-chain connection to as many as eight units.
  2. Direct connection to a single unit controller.

Iziqondiso zokuxhuma kanye nezintambo esimweni ngasinye zichazwe esigabeni esilandelayo. Bheka Ithebula 1 ukuze uthole usayizi wezintambo kanye nemikhawulo yebanga.

QAPHELA: Power is supplied by the MicroTech unit controller. If a separate 24V power supply is desired, please contact either the Daikin Applied Air Technical Response Center at 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com).

I-Daisy-Chain Connection
Sungula ukuxhumana okungokoqobo kusuka kusixhumi esibonakalayo somsebenzisi esikude kuya kusilawuli seyunithi ye-MicroTech.

  1. Connect a twisted pair wire to the CE + and CE – pins of each unit controller and remote user interface (see Figure 4 and Figure 5).
  2. Daisy-chain up to eight MicroTech unit controllers to a single remote user interface. See Figure 5 for wiring details. Note the wire size and distance limitations provided in Table 1.
  3. Cycle power to each MicroTech unit controller once the wiring of the remote user interface is complete.

QAPHELA: Downloading and communication using the daisy- chain connection may be slower than for the RJ45 (Ethernet) direct connection.

Ithebula 1: Wiring Specifications

Ukuxhumana kwebhasi CE+, CE-, not interchangeable
Isikhumulo 2-screw connector
Ubukhulu. ubude 1000 ft (305 m)
Uhlobo lwekhebula
Wiring distance up to 500 ft Twisted pair, shielded cable 16 AWG
Wiring distance between 500 – 1000 ft Twisted pair, shielded cable 14 AWG
Ibanga lezintambo ngaphezu kwe-1000 ft Not currently supported. Contact the appropriate Daikin Applied Technical Response Center for assistance.

DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (4) DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (5)

Ukuxhumana Okuqondile
Isixhumi esibonakalayo somsebenzisi esikude singafakwa intambo ngokuqondile kusilawuli seyunithi eyodwa ye-MicroTech ngoxhumo olujwayelekile lwe-RJ45 (Ethernet).

Inqubo

  1. Locate the connector location as shown in Figure 6
  2. Follow Figure 6 for connection details. Note the distance limitations provided.
  3. Cycle power to the unit(s) once the wiring of the remote user interface is complete.

DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (6)

QAPHELA: Power is supplied by the unit controller. If a separate 24V power supply is desired, please contact either the Daikin Applied Air Technical Response Center at 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com).

Ukusebenzisa i-Remote User Interface

Izici ze-Hardware
Ikhiphedi/isibonisi sokusetshenziswa okukude komsebenzisi siqukethe isibonisi sezinhlamvu ezingu-8 nezingu-30, isondo lokuzulazula elithi "push and roll", kanye nezinkinobho ezintathu: I-alamu, Imenyu, kanye Nemuva (Umfanekiso 7).

  • Turn the navigation wheel clockwise (right) or counterclockwise (left) to navigate between lines on a screen and also to increase and decrease changeable values when editing. Press down on the wheel to use it as an Enter button.
  • Press the Back button to display the previous page.
  • Press the Home button to return to the main screen from the current page.
  • Press the Alarm button to view imenyu yohlu lwe-alamu.

Ikhiphedi/Izici Zokubonisa

The first line on each page includes the page title and the line  number to which the cursor is currently “pointing.” The line numbers are X/Y to indicate line number X of a total of Y lines for that page. The left most position of the title line includes an “up” arrow to indicate there are pages “above” the currently displayed items, a “down” arrow to indicate there are pages “below” the currently displayed items or an “up/down” arrow to indicate there are pages “above and below” the currently displayed page. Each line on a page can contain status-only information or include changeable data fields. When a line contains status-only information and the cursor is on that line, all but the value field of that line is highlighted meaning the text is white with a black box around it. When the line contains a changeable value and the cursor is at that line, the entire line is highlighted.
Ulayini ngamunye osekhasini ungase futhi uchazwe ngokuthi "gxuma", okusho ukuthi ukusunduza isondo lokuzulazula kuzodala "ukweqa" ekhasini elisha. Umcibisholo uboniswa kwesokudla esikude somugqa ukukhombisa ukuthi umugqa "weqa" futhi wonke umugqa uyagqanyiswa lapho ikhesa ikulowo mugqa.

QAPHELA: Only menus and items that are applicable to the  specific unit configuration are displayed.

Umfanekiso 7: Remote User Interface Main Features

DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (7)

Ama-alamu
Imenyu Yemininingwane Ye-alamu ihlanganisa i-alamu esebenzayo nolwazi lwerekhodi le-alamu. Bheka umfanekiso 8 ukuthola i-example of an active alarm. Also refer to the appropriate MicroTech unit controller Operation Manual (www.DaikinApplied.com) for available alarm options.

Umfanekiso 8: Alarm Details Menu

DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (8)

Amaphasiwedi
Imisebenzi yemenyu yesilawuli seyunithi inamazinga ahlukene okufinyeleleka. Ikhono loku view kanye/noma ukushintsha izilungiselelo kuncike ezingeni lokufinyelela lomsebenzisi kanye nephasiwedi efakiwe. Kunamaleveli amane okufinyelela iphasiwedi:

  1. No password.
  2. Level 2. The highest level of access. Without entering a password, the user has access only to basic status menu items. Entering the Level 2 password (6363) allows similar access as Level 4 with the addition of the Unit Configuration Menu.
  3. Level 4. Entering the Level 4 password (2526) allows similar access as Level 6 with the addition of the Commission Unit Menu, Manual Control, and Service Menu groups.
  4. Level 6. Entering the Level 6 password (5321) allows access to the Alarm Lists Menu, Quick Menu, and the View/Setha iqembu lamamenyu eyunithi.

QAPHELA: Alarms can be acknowledged without entering a password.

Ukufinyelela Ikhasi Lephasiwedi
Ikhasi eliyinhloko lephasiwedi liboniswa lapho isibonisi esibonakalayo somsebenzisi esikude (HMI) siqala ukufinyelelwa.

  1. Cindezela inkinobho ethi Ikhaya.
  2. Press the Back button multiple times, or if the keypad/display has been idle longer than the Password Timeout (default 10 minutes).

Ikhasi eliyinhloko le-password linikeza ukufinyelela kokufaka iphasiwedi, finyelela Imenyu Esheshayo, view i-Unit State yamanje, finyelela izinhlu ze-alamu noma view ulwazi mayelana neyunithi (Umfanekiso 9).

DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (9)

The MicroTech unit controller Operation Manual
(www.DaikinApplied.com) provides additional information about passwords, including how to use the Navigation and Edit Mode settings to access and modify passwords.

Ukucushwa
The following section describes how to set up the HMI so that it can be used to display, configure, or change unit parameters. Refer to the applicable MicroTech unit controller Operation Manual for a detailed description of chiller or rooftop sequence of operation and keypad menu structure when configuring the unit via the remote user interface (www.DaikinApplied.com).

QAPHELA: To toggle between units, press the Back button for five seconds to return to the main screen.

Enza ngendlela oyifisayo Izintandokazi Zomsebenzisi

  1. Turn power on to the unit controller(s). Power to the remote user interface is provided automatically from the MicroTech unit controller(s) through the RJ45 (Ethernet) direct connection.
  2. The main screen with HMI Settings and Controller List appears (Figure 10).
    Sebenzisa isikrini sezilungiselelo ze-HMI ukuze ushintshe izinketho zombala wokukhanya kwangemuva, isikhathi sokuvala ukukhanya kwangemuva, ukugqama, nokukhanya.
    QAPHELA: The main screen can be accessed at any time by pressing the Home button for five seconds.
  3. Press the navigation wheel to select the HMI Settings menu, if desired.

DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (9)

Vumelanisa ne-MicroTech Unit Controller

  1. Press the navigation wheel to select the Controller List screen (Figure 11).
    • The Controller List automatically updates each time the remote user interface is powered up so that information is synchronized from the main unit controller.
    • The Controller List screen displays the unit controller(s) connected to the remote user interface. This screen allows the user to select between units, if more than one unit is connected to the remote user interface
    • DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (11)QAPHELA: Iyunithi eyodwa ivela esikrinini njengendlela yokukhetha uma kuphela isilawuli seyunithi esisodwa esixhunywe kusixhumi esibonakalayo somsebenzisi esikude.
  2. Turn the navigation wheel clockwise and then press down to select the desired unit.
    • The Information screen appears as the remote user interface performs a download sequence to import the necessary information from the main unit controller. A status bar appears on the Downloading the Objects screen to indicate that the download is in process (Figure 12).
      QAPHELA: Refer to the Troubleshooting section if the remote user interface appears to “freeze” during the initial downloading sequence.DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (12)
  3. Once the first unit has been downloaded, select the next unit controller, if applicable. The download process is required for each unit controller connected to the remote user interface.
  4. Press the Home button for five seconds to return to the main screen.
    QAPHELA: The Downloading the Objects sequence generally takes a minute or less when direct-connecting to a single unit. However, the downloading sequence takes longer when using the daisy-chain connection.
    Uma ukulandelana kokulanda sekuqediwe, Isikrini Esiyinhloko sesilawuli seyunithi siyavela kusixhumi esibonakalayo somsebenzisi esikude. Kuleli qophelo, isikhombimsebenzisi esikude nesilawuli seyunithi kuyavunyelaniswa.
  5. Access and adjust the same parameters that are available via the unit controller keypad/display. Refer to the applicable MicroTech unit controller Operation Manual for the keypad menu structure and detailed description the unit controller sequence of operation (www.DaikinApplied.com).

Inqubo Yokuthuthukisa I-Firmware

Landela lezi zinyathelo ukuze ubuyekeze isixhumi esibonakalayo somsebenzisi esikude (HMI) firmware (.bin) file.

QAPHELA: The upgrade procedure requires the use of an SD memory card no larger than 8GB with a FAT32 file ifomethi yesistimu.

QAPHELA: Isibuyekezo senkambu asenzeki kumayunithi ane-v1.07 firmware. Xhumana ne-Daikin Applied Air Technical Response Centre ku 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com) ukuthola usizo.

Ithuthukisa isuka ku-VVS10 iye enguqulweni entsha

  1. Layisha i-firmware file, POL12289.bin, kukhadi le-SD kumkhombandlela wempande ngaphandle kokunye files.
  2. Insert the SD Card into the MicroTech unit controller. The unit controller must be powered-up and running.
  3. Connect the HMI DM to the unit controller.
  4. Press the back button of the HMI DM until the “HMI Setting and Local Connection” page appears.
    • Choose the HMI Setting. Scroll to the end of this page and the “Firmware Update” option appears.
    • Push and roll to YES. Push the knob of the HMI DM again.
  5. The “Now Firmware Updating” message appears on the user HMI display.
    Ungawasusi amandla kusilawuli seyunithi.
  6. After successful upgrade of the firmware, the HMI DM goes back to the normal HMI page.
  7. Follow steps 1-4 to upgrade firmware for each HMI on a daisy-chain network. Please be aware that each remote user interface must use the same firmware version.

Ukuxazulula inkinga

Lesi sigaba siqukethe ulwazi oluwusizo, imibuzo evame ukubuzwa, namanye amathiphu ahlobene nesixhumi esibonakalayo somsebenzisi.

Ithebula 2: Troubleshooting Guide

Inkinga Isixazululo
 During the initial download sequence, the keypad/display appears to freeze up and a “Loading…. Lost Connection” message appears. The remote user interface is stuck  in the downloading sequence due to incompatibility with v1.07 application software. The remote user interface must be updated to v10.22 or newer application software. Contact Daikin Applied Air Technical Response at 800-432-1342 ukuze uthole eminye imiyalelo.
 The remote user interface has been connected to the MicroTech unit controller but the display remains blank after power-up.  Qinisekisa ukuthi isilawuli seyunithi sinamandla. Hlola izintambo kusukela kusilawuli seyunithi kuya kusixhumi esibonakalayo somsebenzisi esikude. Qaphela ukuthi okokufaka nokuphumayo kuzwela i-polarity.
Isixhumi esibonakalayo somsebenzisi esikude sibhekene nokulahlekelwa ukuxhumana. Isizinda kungenzeka sibe "namandla angcolile" noma umsindo kagesi obangela ukulahleka kokuxhumana. Bona ngezansi ukuze uthole imiyalelo eyengeziwe.
  1. Access the Power Bus menu on the MicroTech unit controller by the following keypad menu path: service menu/HMI setup/PBusPwrSply=ON (default). See Figure 13.
  2. Set the default Power Bus supply.
    • For the first and last units on the daisy-chain trunk, leave the Power Bus supply at the default of ON.
    • For all other units within the daisy chain trunk, set the Power Bus supply to the OFF position.

DAIKIN-1005-7-MicroTech-Unit-Remote-Controller- (13)

Amathiphu Awusizo
Ochwepheshe besevisi bavame ukukuthola kulula ukuba nekhiphedi/izibonisi ezimbili ezixhunywe kusilawuli seyunithi eyodwa. Ukusebenzisa ukusethwa kwesikrini esihlukanisayo kwenza kube nokwenzeka view izinto zemenyu eziningi ngesikhathi esisodwa ngesikhathi sokuqala futhi nangezinjongo zokuxilonga.

Vele uxhume kalula isixhumi esibonakalayo sokuqala somsebenzisi ngoxhumano oluqondile lwe-RJ45, bese usebenzisa ikhebula elisontekile elinezintambo ezimbili ukuze uxhume kukhiphedi/isibonisi sesibili.

Umlando Wokubuyekeza

Buyekeza Usuku Izinguquko
I-IM 1005 Januwari 2010 Ukukhishwa kokuqala
I-IM 1005-1 Septhemba 2010 Added Daikin Trailblazer® chiller model AGZ-D
I-IM 1005-2 Mashi 2012 Added Rebel® packaged rooftop model DPS. Updated Figure 3 with labels and connector cables.
I-IM 1005-3 Novemba 2016 Added models AWV Pathfinder® chiller and AGZ-E Trailblazer® chiller, added RJ45 direct connection option, corrected bus wiring distance limitations, Troubleshooting section, Daikin branding and formatting updates
I-IM 1005-4 Januwari 2018 Kungezwe amamodeli e-WME & WWV apholile.
I-IM 1005-5 Agasti 2019 Updated connections
I-IM 1005-6 Juni 2023 Ibhrendi nezinye izibuyekezo zokufometha.
I-IM 1005-7 Julayi 2025 Updated contact information, added Daikin Trailblazer® chiller model AMZ, and removed model lists from front cover.

I-Daikin Applied Training and Development
Manje njengoba usutshale imali kumishini yesimanje, esebenza kahle ye-Daikin Applied, ukunakekelwa kwayo kufanele kube yinto ehamba phambili. Ukuze uthole ulwazi lokuqeqeshwa kuyo yonke imikhiqizo ye-Daikin Applied HVAC, sicela usivakashele ku www.DaikinApplied.com bese uchofoza Ukuqeqesha, noma shayela 540-248-9646 futhi ucele uMnyango Wokuqeqesha.

Iwaranti

Zonke izinto zokusebenza ze-Daikin Applied zithengiswa ngokulandela imigomo nemibandela yayo evamile yokuthengisa, okuhlanganisa Iwaranti Yomkhiqizo Enomkhawuko. Xhumana nommeleli wakho wendawo we-Daikin Applied ukuze uthole imininingwane yewaranti. Ukuze uthole omele i-Daikin Applied, vakashela ku www.DaikinApplied.com.

Amasevisi E-Aftermarket
Ukuze uthole ihhovisi lendawo yangakini, vakashela www.DaikinApplied.com noma shayela u-800-37PARTS (800-377-2787). Ukuze uthole ihhovisi lensizakalo yangakini, vakashela www.DaikinApplied.com noma shayela 800-432-1342.
Lo mbhalo uqukethe ulwazi lwamanje lomkhiqizo kusukela kulokhu kuphrintwa. Ukuze uthole ulwazi olusha kakhulu lomkhiqizo, sicela uye ku www.DaikinApplied.com.
Imikhiqizo ekhiqizwa endaweni eqinisekisiwe ye-ISO.

imibuzo ejwayelekile ukubuzwa

How many units can be controlled per remote interface?

The remote user interface can handle up to eight units per interface.