1. Isingeniso
The Extech 382252 is a comprehensive Earth Ground Resistance Tester Kit designed for accurate measurement of earth ground resistance. This kit provides three selectable ranges for earth ground resistance: 20 Ohms (Ω), 200 Ohms (Ω), and 2000 Ohms (Ω). Beyond earth ground testing, the device also functions as a multimeter, capable of measuring AC/DC Voltage, Resistance, and Continuity. It features automatic zero adjustment for ease of use. This manual provides detailed instructions for the safe and effective operation, maintenance, and troubleshooting of your Extech 382252.
2. Ulwazi Lokuphepha
Isexwayiso: Improper use of this meter can cause damage, shock, injury, or death. Read and understand all safety information and operating instructions before using this instrument. Always adhere to local and national safety codes.
- Do not exceed the maximum input limits for any function.
- Exercise extreme caution when working with live electrical circuits.
- Ensure the meter is in good working condition and free from damage before use.
- Sebenzisa njalo umsebenzi kanye nobubanzi obufanele ukuze ulinganise.
- Replace batteries when the low battery indicator appears to ensure accurate readings.
- Keep hands and fingers away from test probe tips when making measurements.
- Do not operate the meter in explosive atmospheres or in the presence of flammable gases or dust.
3. Okuqukethwe Kwephakheji
Qinisekisa ukuthi zonke izinto zikhona futhi azilimele lapho kukhishwa:
- Extech 382252 Earth Ground Resistance Tester
- Test Leads (set)
- Auxiliary Earth Bars (2 pieces)
- Ukuthwala Ikesi
- Protective Rubber Holster
- 1.5V AA Batteries (6 pieces)

Image 1: The Extech 382252 Earth Ground Resistance Tester Kit, showing the main unit, test leads, two auxiliary earth bars, and the carrying case.
4. Izici zomkhiqizo
The Extech 382252 offers the following key features:
- Earth Ground Resistance measurement in three ranges: 20Ω, 200Ω, and 2000Ω.
- I-AC/DC Voltage measurement capabilities.
- Resistance and Continuity testing functions.
- Automatic zero adjustment for accurate readings.
- Isibonisi se-LCD esikhulu, esifundeka kalula.
- Data Hold function to freeze displayed readings.
- Backlight for visibility in low-light conditions.
- Durable protective rubber holster.

Isithombe 2: Ngaphambili view of the Extech 382252 Earth Ground Resistance Tester, highlighting its display, function dial, and control buttons.
5. Setha
5.1 Ukufakwa kwebhethri
- Ensure the meter is powered off.
- Locate the battery compartment cover on the rear of the meter.
- Use a screwdriver to remove the screw(s) securing the cover.
- Insert six (6) 1.5V AA batteries, observing correct polarity (+/-).
- Shintsha isembozo segumbi lebhethri bese usiqinisa ngezikulufo.
5.2 Ukuxhumanisa Imihlahlandlela Yokuhlola
Connect the test leads to the appropriate input jacks on the meter for the desired measurement function. For earth ground resistance testing, specific connections involving the auxiliary earth bars will be detailed in the operating instructions.
6. Iziqondiso Zokusebenza
6.1 Vula/Vala amandla
Rotate the function dial from the 'OFF' position to any desired measurement function to power on the meter. To power off, rotate the dial back to the 'OFF' position.
6.2 Automatic Zero Adjustment
The meter features automatic zero adjustment. When selecting a resistance range, the meter will automatically adjust to zero, compensating for lead resistance. Ensure test leads are not shorted or open during this process for accurate zeroing.
6.3 Umsebenzi wokubamba idatha
Press the 'HOLD' button to freeze the current reading on the display. Press it again to release the hold and resume live readings.
6.4 Umsebenzi we-Backlight
Press the backlight button (often indicated by a light bulb icon) to illuminate the display for better visibility in dark environments. Press it again to turn off the backlight.
7. Earth Ground Resistance Measurement
The Extech 382252 uses the 3-wire (or Fall-of-Potential) method for earth ground resistance measurements. This method requires the use of the two auxiliary earth bars provided.
7.1 Measurement Procedure (3-Wire Method)
- Ukulungiselela: Ensure the circuit under test is de-energized and safely isolated.
- Placement of Auxiliary Earth Bars:
- Drive the first auxiliary earth bar (P) into the ground at a suitable distance from the earth electrode (E) being tested.
- Drive the second auxiliary earth bar (C) into the ground at a further distance from P, ensuring all three points (E, P, C) are in a straight line. Typical distances are 5-10 meters (15-30 feet) between E and P, and P and C, but may vary based on soil conditions and electrode size.
- Ukuxhuma Ukuhola Kokuhlola:
- Connect the 'E' terminal of the meter to the earth electrode under test.
- Connect the 'P' terminal of the meter to the first auxiliary earth bar (P).
- Connect the 'C' terminal of the meter to the second auxiliary earth bar (C).
- Khetha Ibanga: Rotate the function dial to the desired Earth Ground Resistance range (20Ω, 200Ω, or 2000Ω). Start with the highest range if the resistance value is unknown.
- Perform Test: Press the 'TEST' button. The meter will inject a current and measure the voltage drop to calculate the earth ground resistance.
- Funda Ukukala: The resistance value will be displayed on the LCD.
- Qinisekisa Ukunemba: For critical measurements, it is recommended to repeat the test with the auxiliary earth bars placed at slightly different distances to ensure the reading is stable and accurate.
8. Other Measurements
8.1 AC/DC Voltage Ukukala
- Connect the red test lead to the 'V' input jack and the black test lead to the 'COM' input jack.
- Rotate the function dial to the desired ACV (750V AC) or DCV (1000V DC) range.
- Connect the test probes across the circuit or component to be measured.
- Funda ivolumutage kusibonisi.
8.2 Isilinganiso Sokumelana
- Qinisekisa ukuthi isekethe noma ingxenye ayinamandla.
- Connect the red test lead to the 'V' input jack and the black test lead to the 'COM' input jack.
- Rotate the function dial to the desired Resistance range (e.g., 200Ω, 20kΩ, 200kΩ).
- Connect the test probes across the component.
- Funda inani lokumelana esibonisweni.
8.3 Ukuhlola Ukuqhubeka
- Qinisekisa ukuthi isekethe noma ingxenye ayinamandla.
- Connect the red test lead to the 'V' input jack and the black test lead to the 'COM' input jack.
- Rotate the function dial to the Continuity position (often indicated by a speaker icon).
- Connect the test probes across the component or wire.
- An audible beep indicates continuity (low resistance). The display will show the resistance value.
9. Isondlo
9.1 Ukuhlanza
Wipe the meter with a dry, soft cloth. Do not use abrasives or solvents. Periodically clean the test leads and probes to ensure good electrical contact.
9.2 Ukushintshwa Kwebhethri
When the low battery indicator appears on the display, replace the batteries promptly to maintain measurement accuracy. Refer to Section 5.1 for battery installation instructions.
9.3 Isitoreji
If the meter is to be stored for an extended period, remove the batteries to prevent leakage and damage. Store the meter in its carrying case in a cool, dry environment, away from direct sunlight and extreme temperatures.
10. Ukuxazulula izinkinga
- No Display/Meter Not Powering On: Check battery installation and ensure batteries are fresh. Verify the function dial is not in the 'OFF' position.
- Ukufundwa Okungalungile: Ensure test leads are properly connected and not damaged. Check battery level. For earth ground resistance, verify proper placement and connection of auxiliary earth bars and ensure good contact with the ground.
- Akukho Umsindo Wokuqhubeka: Check if the circuit is truly continuous. Ensure test leads are making good contact.
- Display Shows 'OL' (Overload): Inani elilinganisiwe lidlula ububanzi obukhethiwe. Shintshela kububanzi obuphezulu.
If issues persist after following these steps, contact customer support.
11. Imininingwane
| Ukucaciswa | Inani |
|---|---|
| Ibhrendi | I-Extech |
| Inombolo Yemodeli | 382252 |
| Earth Ground Resistance Ranges | 20Ω, 200Ω, 2000Ω |
| I-AC Voltage Ibanga | Kufika ku-750V AC |
| I-DC Voltage Ibanga | Kufika ku-1000V DC |
| Izindlela Zokumelana | 20Ω, 200Ω, 20kΩ, 200kΩ (typical, check device for full ranges) |
| Ukunemba Kwesilinganiso | +/-0.5% (for certain functions, refer to product manual for specifics) |
| Umthombo wamandla | 6 x 1.5V AA Amabhethri |
| Isisindo sento | 0.69 Kilogram (1.52 pounds) |
| Ubukhulu bomkhiqizo (L x W x H) | 7.9 x 3.6 x 2 amayintshi |
| Izingxenye Ezihlanganisiwe | Test leads, 2 earth bars, carrying case, holster, six 1.5V AA batteries |
| Isilinganiso Sokuphepha | CAT III 1000V, CE |
12. Iwaranti
The Extech 382252 Earth Ground Resistance Tester Kit typically comes with a Iwaranti ekhawulelwe yeminyaka engu-1 from the date of purchase. This warranty covers defects in materials and workmanship under normal use. It does not cover damage resulting from misuse, accident, unauthorized repair, or modification. Please retain your proof of purchase for warranty claims.
13. Ukusekela
For technical assistance, calibration services, or further information regarding your Extech 382252, please refer to the official Extech website or contact their customer support department. Contact details can usually be found on the manufacturer's webisayithi noma kumadokhumenti afakwe nomkhiqizo wakho.