SmartGen HAT361 HAT361C

SmartGen HAT361 HAT361C Dual Power Automatic Switching Controller

Imaniwali yosebenzisayo

Model: HAT361, HAT361C | Brand: SmartGen

1. Isingeniso

The SmartGen HAT360 series dual power automatic transfer switch (ATS) controller, including models HAT361 and HAT361C, is designed with a microprocessor core for precise monitoring and control of dual power systems. It accurately measures two-way voltages, detects abnormalities (such as over/under voltage, over/under frequency, loss of phase, and reverse phase sequence), and intelligently manages the transfer between power sources. This controller integrates an LCD display and digital communication capabilities, providing a user-friendly interface for efficient power management.

The HAT361C model includes RS485 communication for remote control and monitoring via Modbus protocol.

2. Ulwazi Lokuphepha

Sicela ufunde futhi uqonde yonke imiyalelo yokuphepha ngaphambi kokufakwa nokusebenza. Ukwehluleka ukulandela le miyalelo kungabangela ukushaqeka kukagesi, umlilo, noma ukulimala okukhulu.

  • Ensure all power sources are disconnected before performing any installation, wiring, or maintenance.
  • Abasebenzi abafanelekayo kuphela okufanele bafake futhi balungise le mishini.
  • Verify all wiring connections are correct and secure according to the provided diagrams.
  • Do not operate the controller if it is damaged or malfunctioning.
  • Keep the controller away from moisture, extreme temperatures, and corrosive environments.
  • Qinisekisa ukubeka phansi ngendlela efanele ukuze uvimbele izingozi zikagesi.

3. Umkhiqizo Uphelileview

The HAT361/HAT361C controllers are designed for dual power ATS applications, offering robust features for reliable power transfer.

3.1 Izici Nezimpawu

  • Configurable for 3P4W, 3P3W, 2P3W, or 1P2W AC systems.
  • Intelligent MCU-based monitoring and control.
  • S1/S2 master/slave configuration for auto transfer/restore and non-restore modes.
  • Supports Auto and Manual operation modes.
  • OFF mode disables breaker close/open functions.
  • System type settings for S1 Mains S2 Mains, S1 Gen S2 Mains.
  • Measures and displays 2-way 3-phase voltage, frequency, and alarm status.
  • Suitable for two-breaking, one-breaking, and no-breaking switches.
  • Includes switch re-closing function.
  • RS485 serial communication port (optional on HAT361C) for remote control, measuring, communication, and adjustment via Modbus protocol.
  • I-Overvoltage, ukungasebenzitage, overfrequency, underfrequency, loss of phase, and reverse phase sequence detection.
  • Adjustable thresholds for voltage and frequency abnormalities.
  • Manual test function for genset start/stop.
  • LED indicators for current ATS close status, power status, mode (manual/auto/OFF), and alarms.
  • Idizayini ehlukanisiwe yezintambo ezingu-2 ze-N.

3.2 Ukuhlelwa Kwephaneli Engaphambili

The front panel provides visual indicators and control buttons for easy operation.

SmartGen HAT361 Front Panel

Figure 1: SmartGen HAT361 Front Panel. Shows S1/S2 indicators, LOAD indicator, OFF button, Auto/Manual buttons, S1 Close/Open/S2 Close buttons, and the SmartGen display.

SmartGen HAT361C Front Panel

Figure 2: SmartGen HAT361C Front Panel. Similar layout to HAT361, indicating the 'C' model variant.

4. Ukusetha nokufakwa

Careful installation and wiring are crucial for the proper functioning of the ATS controller.

4.1 Controller Dimensions and Panel Cutout

The controller is designed for panel mounting. Ensure the panel cutout matches the specified dimensions.

IsilinganisoInani
Ubukhulu bekesi132mm x 102mm x 49mm
Iphaneli yokusika132mm x 102mm

4.2 Rear Panel and Terminal Description

The rear panel houses all necessary connection terminals. Refer to the diagrams and table below for proper wiring.

SmartGen HAT361 Rear Panel Wiring Terminals

Figure 3: SmartGen HAT361 Rear Panel with Wiring Terminals. Shows inputs for S1/S2 AC voltage, GEN START, S1/S2 CLOSE INPUT, RS485, and AUX OUTPUT.

HAT361C Panel Diagram

Figure 4: HAT361C Panel Diagram. Detailed view of terminal numbering on the rear panel.

Cha.IntoPhawula
1A1AC 3 phase 4 wire voltage input of S1 (For single phase input, only connect A1,N1)
2B1
3C1
4N1
5A2AC 3 phase 4 wire voltage input of S2 (For single phase input, only connect A2,N2)
6B2
7C2
8N2
9CHAATS supply power N (Provide supply power for ATS)
10CHAATS supply power L (Capacity: 12A 250VAC)
11I-LOATS supply power L (NC for terminal 10 of HAT361)
12CHA
13COMOutput common port
14S1 CLOSES1 close output (Capacity: 10A 250VAC)
15S2 CLOSES2 close output (Capacity: 10A 250VAC)
16S1 OPEN OUTPUTS1 open output (Capacity: 10A 250VAC)
17S2 OPEN OUTPUTS2 open output (Capacity: 10A 250VAC)
18GEN STARTGenset start output (Capacity: 7A 250VAC)
19COMInput common port
20FORCE OPENForced open input (Connect GND of input common port)
21COMInput common port
22S2 CLOSE INPUTS2 close input (Connect GND of input common port)
23COMInput common port
24S1 CLOSE INPUTS1 close input (Connect GND of input common port. Users need to connect this terminal to terminal 27 based on on-site network arrangement, used to connect with the 120Ω resistor inside the controller)
25TRRS485 matching resistor (120Ω impedance matching resistor inside the controller)
26TR
27B(-)Imbobo yokuxhumana ye-RS485
28A(+)
29COMImbobo evamile
30I-AUX INPUTAux. input (Connect GND of input common port)
31I-AUX OUTPUTAux. output (Capacity: 10A 250VAC)
32

4.3 Imidwebo Yezintambo Ezijwayelekile

Below are typical application wiring diagrams. Always consult local electrical codes and standards.

4.3.1 SGG-N/T Application Diagram

SGG-N/T Application Wiring Diagram

Figure 5: SGG-N/T Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for SGG-N/T type switches. Note: Suitable for HAT363 (No Breaking) controller model.

4.3.2 ATYS Application Diagram

ATYS Application Wiring Diagram

Figure 6: ATYS Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for ATYS type switches. Note: Suitable for HAT363 (One breaking) controller model.

4.3.3 PHETENG Application Diagram

PHETENG Application Wiring Diagram

Figure 7: PHETENG Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for PHETENG type switches. Note: Suitable for HAT363 (Two breakings) controller model.

4.3.4 Motor Type Application Diagram

Motor Type Application Wiring Diagram

Figure 8: Motor Type Application Diagram. Illustrates connections for S1 Power Input, S2 Power Input, Load, ATS Controller, and Remote Start for Motor Type switches. Note: Suitable for HAT361/HAT363 (One breaking) controller model.

5. Ukusebenza

This section details the operational modes, key functions, and display information of the controller.

5.1 Indicator Display

The front panel LEDs provide immediate status feedback.

InkombaIncazelo
S1 Power IndicatorExtinguishes when S1 power blackout; Illuminates when S1 power is normal.
S1 Close IndicatorFlashes when S1 power is abnormal (over/under voltage, under/over frequency, loss of phase, reverse phase sequence); Illuminates when S1 is closed, otherwise, it extinguishes.
S2 Power IndicatorIlluminates when S2 power is normal; Extinguishes when S2 power blackout.
S2 Close IndicatorFlashes when S2 power is abnormal (over/under voltage, under/over frequency, loss of phase, reverse phase sequence); Illuminates when S2 is closed, otherwise, it extinguishes.
Inkomba ye-alamuIlluminates when there is an alarm.
OFF Mode IndicatorIlluminates in OFF mode, extinguishes in other modes.
Inkomba yemodi ye-AutoIlluminates in Auto mode, extinguishes in other modes.
Inkomba Yemodi YemanuwaliIlluminates in Manual mode, extinguishes in other modes.

5.2 Key Function Description

The controller features several keys for navigation and control.

IsithonjanaUkhiyeIncazelo Yomsebenzi
UpIn main interface, scrolls up the screen; In menu interface, moves cursor up or increases number.
PhansiIn main interface, scrolls down the screen; In menu interface, moves cursor down or reduces number.
*/okSet/Confirm/Lamp IsivivinyoIn main interface, moves cursor and confirms settings. Long press tests lamps (all white screen, all LEDs illuminate, alarms reset).
VALIWEVALIWEEnters OFF mode, controller exits control.
OkuzenzakalelayoImodi ye-AutoEnters Auto mode.
S1 CloseS1 CloseActive in manual mode; closes S1 outputs, S1 takes load.
VulaVulaActive in manual mode; load disconnects.
S2 CloseS2 CloseActive in manual mode; closes S2 outputs, S2 takes load.
ImanuwaliImodi yeManuwaliEnters Manual mode.

5.3 Isibonisi se-LCD

The LCD provides detailed information about the system status.

OkuqukethweIncazelo
Isibonisi Esibonakalayo Esiyinhloko
S1 BlackoutS1 voltage isimo
S2 BlackoutS2 voltage isimo
LayishaATS status
Genset WorkingGenset isimo
Imodi yeManuwaliUmugqa wesimo
I-Volt
LL1S1 line voltage
LL2S2 line voltage
I-Volt
I-LN1S1 phase voltage
I-LN2S2 phase voltage
I-Freq
F1S1 frequency
F2S2 frequency
Ukulandelana Kwesigaba
P1S1 Phase Sequence
P2S2 Phase Sequence
S1 Failed to CloseUlwazi Lwe-alamu

5.4 Izindlela Zokusebenza

5.4.1 Imodi Yezandla

To enter Manual Mode, press the Imanuwali key. The manual status indicator will illuminate. In this mode, you can manually control the S1 and S2 breakers:

  • S1 Close: If the load is open, S1 closes and supplies power to the load.
  • S2 Close: If the load is open, S2 closes and supplies power to the load.
  • Vula: Disconnects the load from both power sources.

5.4.2 Imodi Yokuzenzakalela

To enter Auto Mode, press the Okuzenzakalelayo key. The auto status indicator will illuminate. In Auto Mode, the controller automatically transfers the switch based on the status of S1 and S2 power, transfer priority, and auto transfer/restore settings to ensure continuous power supply to the load.

5.4.3 Auto Transfer/Restore Logic

The controller follows specific logic for automatic transfer and restoration. An example of 'S1 master' and 'S2 Mains S2 Gen' control logic is illustrated below:

Auto Transfer/Restore Flowchart

Figure 9: Auto Transfer/Restore Flowchart. Details the sequence of events for S1 Normal, S1 Abnormal, S2 Normal, and S2 Abnormal conditions, including delays and generator start signals.

5.4.4 Auto Transfer Non-Restore (Mutual Backup Active) Logic

This mode is used when both power sources act as mutual backups.

Auto Transfer Non-Restore Flowchart

Figure 10: Auto Transfer Non-Restore (Mutual Backup Active) Flowchart. Illustrates the logic for non-restorative transfer between S1 and S2.

6. Imininingwane

Detailed technical parameters for the HAT361/HAT361C controllers.

6.1 Amapharamitha wezobuchwepheshe

IzintoOkuqukethwe
I-Operating VoltageAC supply, voltage range AC170-277V
Ukusetshenziswa kwamandla≤5W (Standby mode: ≤2W)
I-AC Voltage Ukufaka3P4W (L-N): AC170V~AC277V
3P3W (L-L): AC170V~AC277V
2P3W (L-N): AC170V~AC277V
1P2W (L-N): AC170V~AC277V
Kulinganiswe ngoVoltageKukalwe: 380V
Imvamisa elinganiselweRange: 50Hz/60Hz
UkunembaVoltage: ±2%, Frequency: ±0.1Hz
Vala okukhiphayo kwe-Relay10A AC250V volts free output
I-Axiliary Relay Output10A AC250V volts free output
Genset Crank Relay Output7A AC250V volts free output
LONG Relay Output12A AC275V Active output
LINKSmartGen special interface for program upgrade, parameter configuration
RS485Modbus-RTU communication protocol, max communication distance is 1000m (HAT361C only)
Izinga LokwakhaMeet GB/T 14048.11-2016 and IEC/EN 60947-6-1
Isidingo SokuphephaMeet EN 61010-1 (installation category (overvoltage type) III, 300V, pollution degree 2), altitude ≤3000m
Ubukhulu bekesi132mm x 102mm x 49mm
Iphaneli yokusika132mm x 102mm
Izinga Lokushisa Lokusebenza(-25~+70)°C
Umswakama Osebenzayo(20~90)%RH
Izinga Lokushisa Lesitoreji(-30~+80)°C
Izinga LokuvikelaIphaneli yangaphambili IP40
Amandla e-InsulationFaka i-AC2.2kV voltage phakathi kwevolumu ephezulutagi-terminal kanye nevolumu ephansitage terminal and the leakage current is not more than 3mA within 1min; insulation resistor 100MΩ
Isisindo0.59kg

6.2 Ukuqhathanisa Isibonelo

IntoI-HAT361HAT361CI-HAT363HAT363C
Inputs (L1,N,70V-277V)3+13+13+13+1
Outputs (Fixed + Aux.)4+14+15+15+1
Genset Control
RS485
LONG Output

Note: HAT361/HAT361C defaults to one breaking. HAT363/HAT363C defaults to two breakings.

7. Isondlo

To ensure the longevity and reliable operation of your SmartGen ATS controller, follow these general maintenance guidelines:

  • **Regular Inspection**: Periodically check the controller for any visible damage, loose connections, or signs of overheating.
  • **Cleaning**: Keep the controller's front panel and ventilation openings clean and free of dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • **Firmware Updates**: Check the manufacturer's website for any available firmware updates. Follow the instructions carefully if performing an update.
  • **Environmental Conditions**: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature component failure.
  • **Wiring Integrity**: Annually inspect all wiring connections for tightness and corrosion. Loose connections can lead to intermittent operation or damage.

8. Ukuxazulula izinkinga

If you encounter issues with your HAT361/HAT361C controller, consider the following general troubleshooting steps:

  • **No Power/Display Off**: Check the power supply to the controller. Ensure all power input terminals are correctly wired and receiving the specified voltage.
  • **No Automatic Transfer**: Verify that the controller is in 'Auto Mode'. Check the status of S1 and S2 power sources on the display. Ensure all abnormal conditions (over/under voltage, frequency) are cleared. Review the wiring for S1/S2 voltage inputs and breaker control outputs.
  • **Manual Operation Fails**: Ensure the controller is in 'Manual Mode'. Check the wiring to the S1/S2 close and open outputs.
  • **Alarm Indicator On**: Check the LCD display for specific alarm messages. Refer to the 'Indicator Display' section for common alarm meanings. Address the underlying issue (e.g., voltage abnormality, frequency deviation).
  • **Communication Issues (HAT361C)**: Verify RS485 wiring (A+, B-, GND) is correct and secure. Ensure the 120Ω matching resistor is properly connected if required by your setup. Check communication settings (baud rate, parity) on both the controller and the connected device.
  • **Incorrect Readings**: Confirm that the voltage and current transformer ratios (if applicable) are correctly configured in the controller's settings.

If the problem persists after performing these checks, contact technical support.

9. Amathiphu Womsebenzisi

  • **Parameter Configuration**: Take time to properly configure all parameters, especially voltage and frequency thresholds, to match your specific power system requirements.
  • **Test Regularly**: Periodically test the automatic transfer function to ensure the system operates as expected during a power outage.
  • **Backup Settings**: If possible, record or back up your controller's configuration settings for quick restoration in case of a reset or replacement.
  • **Environmental Protection**: While the front panel is IP40 rated, ensure the overall installation protects the controller from excessive dust and moisture, especially the rear terminals.

10. Iwaranti kanye Nokusekela

For warranty information, technical support, or service inquiries, please contact your authorized SmartGen dealer or the manufacturer directly. Keep your purchase receipt and product serial number handy when contacting support.

Imininingwane Yokuxhumana Nomkhiqizi:

  • Web: www.smartgen.cn/
  • Email: sales@smartgen.cn

I-SmartGen inelungelo lokushintsha okuqukethwe kulo mbhalo ngaphandle kwesaziso sangaphambili.

Amadokhumenti Ahlobene - HAT361 HAT361C

Ngaphambiliview SmartGen HGM9420N_HGM9420LT Genset Controller User Manual
Comprehensive user manual for the SmartGen HGM9420N and HGM9420LT Genset Controllers. Learn about features, specifications, operation, wiring, protections, and troubleshooting for advanced genset automation, AMF, and synchronous transfer applications.
Ngaphambiliview I-SmartGen HAT520N ATS Isilawuli Incwadi Yomsebenzisi
User manual for the SmartGen HAT520N Dual Power ATS Controller, detailing its performance, specifications, panel operations, parameter configuration, installation, and troubleshooting.
Ngaphambiliview HAT72 ATS Controller User Manual
User manual for the Smartgen HAT72 Automatic Transfer Switch (ATS) Controller, detailing its features, technical parameters, operation, terminal connections, and typical wiring for mains and generator power switching. Designed for reliable automatic power transfer.
Ngaphambiliview Isilawuli se-SmartGen HAT310 ATS: Imanuwali Yomsebenzisi Nemininingwane Yobuchwepheshe
Imanuwali yomsebenzisi yesilawuli se-SmartGen HAT310 Automatic Transfer Switch (ATS). Ukucaciswa kwemininingwane, imisebenzi yephaneli, ukusebenza, imidwebo yezintambo, ukufakwa, nokuxazulula izinkinga zokuphathwa kwamandla okuthembekile.
Ngaphambiliview SmartGen HAT880 Series Dual Power Bypass ATS Controller User Manual
This user manual provides detailed operational and technical guidance for the SmartGen HAT880 Series Dual Power Bypass ATS Controller (HAT880/HAT880S), covering its features, specifications, operation, installation, and troubleshooting for reliable dual power management.
Ngaphambiliview I-SmartGen HAT560NC Series ATS Controller Manual
User manual for the SmartGen HAT560NC Series Automatic Transfer Switch (ATS) Controller. This manual provides detailed information on the controller's features, operation, specifications, installation, and troubleshooting.